Power Supply
- 90 to 250VA
- 47 to63Hz
- 20 to 28 VAC
- 47-63Hz / 11 to 40 VDC
Power Consumption
- L22: 8VA, 4W maximum
- L62: 10VA, 5W maximum
- L42: 12VA, 6W maximum
Signal Input Type
- Thermocouple (J, K, T, E, B, R, S, N, L, U, P, C, D)
- RTD(Pt100(DIN)
- Pt100(JIS)
- Current(mA)
- Voltage (V, mV)
Signal Input Sampling Rate
Signal Input Maximum Rating
- -2VDC minimum,
- 12VDC maximum
Signal Input - Input Characteristics (Type: Range, Accuracy @ 25°C, Input Impedance)
- J: -120°C to 1000°C ( -184°F to 1832°F), ±2°C, 2.2 MΩ
- K: -200°C to 1370°C (-328°F to 2498°F), ±2°C, 2.2 MΩ
- T: -250°C to 400°C ( -418°F to 752°F), ±2°C, 2.2 MΩ
- E: -100°C to 900°C ( -148°F to 1652°F), ±2°C, 2.2 MΩ
- B: 0°C to 1820°C (32°F to 3308°F), ±2°C (200°C to 1800°C), 2.2 MΩ
- R: 0°C to 1767.8°C (32°F to 3214°F), ±2°C, 2.2 MΩ
- S: 0°C to 1767.8°C (32°F to 3214°F), ±2°C, 2.2 MΩ
- N: -250°C to 1300°C ( -418°F to 2372°F), ±2°C, 2.2 MΩ
- L: -200°C to 900°C ( -328°F to 1652°F), ±2°C, 2.2 MΩ
- U: -200°C to 600°C (-328°F to 1112°F), ±2°C, 2.2 MΩ
- P: 0°C to 1395°C (32°F to 2543°F), ±2°C, 2.2 MΩ
- C: 0°C to 2300°C (32°F to 4172°F), ±2°C, 2.2 MΩ
- D: 0°C to 2300°C (32°F to 4172°F), ±2°C, 2.2 MΩ
- Pt100(DIN): -210°C to 700°C ( -346°F to 1292°F), ±0.4°C, 1.3KΩ
- Pt100(JIS): -200°C to 600°C ( -328°F to 1112°F), ±0.4°C, 1.3KΩ
- mA: -3mA to 27mA, ±0.05%, 2.5Ω
- VDC: -1.3VDC to 11.5VDC, ±0.05%, 1.5MΩ
- mV: 0 to 50mV, ±0.05%, 2.2 MΩ
Signal Input Temperature Effect
- 1.5μV /°C for all inputs except mA input
- 3.0μV /°C for mA
Signal Input Sensor Lead Resistance Effect
- Thermocouple: 0.2 μV / Ω; 3-wire RTD: 2.6°C /Ω of difference of resistance of two leads
- 2-wire RTD: 2.6°C /Ω of sum of resistance of two leads
Signal Input Burn-out Current
Signal Input Sensor Break Detection
- Sensor open for Thermocouple
- RTD and mV inputs
- Sensor short for RTD input
- Below 1mA for 4-20mA input
- Below 0.25VDC for 1 - 5VDC input
- Not available for other inputs.
Signal Input Sensor Break Response Time
- Within 4 seconds for Thermocouple,
- RTD and mV inputs
- 0.1 second for 4-20mA and 1 - 5VDC inputs
Digital Filter Time Constant
- 0,0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 Seconds
- Programmable
Event Input Logic Low
- -10VDC minimum
- 0.8VDC maximum
Event Input Logic High
- 2VDC minimum
- 10VDC maximum
Event Input Functions
- Remote lock
- Remote reset output1
- HSP2
- LSP2
- HLS2
- HSP3
- LSP3
- HLS3
- Reset alarm1
- Reset alarm2
- Reset alarm3
- Reset all alarms
- Cancel latch
- Reset reference data
Output 1 /Output 2 Limit Control Function
- High Limit
- Low Limit and High / Low Limit
Output 1 /Output 2 Relay Type
Output 1 /Output 2 Relay Rating
- 2A
- 240V AC
- 200000 Life cycles for resistive load
Output 1 /Output 2 Pulsed Voltage
- Source voltage 5VDC
- Current limiting resistance 66Ω
Output 1 /Output 2 Temperature Effect
Alarm Maximum Rating
- 2A
- 240VAC
- 200000 Life cycles for resistive load
Alarm Alarm Mode
- Latching
- Normal
- Latching reverse
- Normal reverse
Data Communication Interface
Data Communication Protocol
Data Communication Address
Data Communication Baud Rate
Data Communication Parity Bit
Data Communication Stop Bit
Data Communication Data Length
Analog Retransmission Output Signal
Analog Retransmission Resolution
Analog Retransmission Accuracy
- ±0.05% of Span ± 0.0025% / °C
Analog Retransmission Load Resistance
- 0 to 500Ω for current output
- 10KΩ minimum for voltage output
Analog Retransmission Output Regulation
- 0.01% for full load change
Analog Retransmission Output Setting Time
- 0.1Second (stable to 99.9%)
Analog Retransmission Isolation Breakdown
Analog Retransmission Integral Linearity Error
Analog Retransmission Temperature Effect
Analog Retransmission Saturation Low
Analog Retransmission Saturation High
- 22.2mA or 5.55V,11.1V min
Analog Retransmission Linear Output Ranges
- 0-22.2mA (0-20mA/4-20mA)
- -5.55VDC (0-5VDC, 1-5VDC)
- -11.1VDC (0 - 10VDC)
User Interface Display Type
User Interface Number of Display
User Interface Upper Display Size
- L22: 0.31” (8mm)
- L62: 0.58” (15mm)
- L42: 0.98” (25mm)
User Interface Lower Display Size
- L22: 0.25” (6.5mm)
- L62: 0.3” (7.8mm)
- L42: 0.55” (14mm)
Programming Port Interface
Programming Port PC Communication Function
Humidity
- 0 to 90 % RH (Non-Condensing)
Dielectric Strength
- 2000VAC
- 50/60 Hz for 1 minute
Vibration Resistance
- 10 to 55 Hz
- 10m/s2 for 2 hours
Housing
- Flame retardant polycarbonate
Mounting
- L22: DIN-Rail
- L62: Panel
- L42: Panel
Dimensions
- L22: 22.5 x 96 x 83mm
- L62: 48 x 48 x 59mm
- L42: 96 x 96 x 59mm
Cut Out Dimensions
- L62: 45 x 45mm
- L42: 92 x 92mm
Weight
- L22: 160 grams
- L62: 160 grams
- L42: 290 grams
Safety
- FM Class 3545
- UL/cUL 61010-1 Category QUYX/QUYX7
- ROHS
- REACH
Protective Class
- IP50 for the front panel
- IP20 for rear terminals and housing
- All indoor use